CP1Reading a motor nameplate
Sample condenser fan motor nameplate
- HP
- 1/3
- Volts
- 208-230
- Phase
- 1
- Hz
- 60
- FLA
- 2.2
- RPM
- 1075
- Speeds
- 1
- Frame
- 48Y
- Rotation
- CCWLE, reversible
- Capacitor
- 7.5 µF / 370 VAC
- Enclosure
- TEAO
- Bearings
- Ball
- Max ambient
- 60 °C
- Shaft
- 1/2 in
| Field | Meaning | Matching rule |
|---|---|---|
| HP | Output horsepower. Fan motors run from about 1/10 to 1 HP | Same. A universal replacement may cover a range |
| Volts, phase, Hz | Supply the motor is wound for: 115, 208-230 or 460 V, single or three phase | Exact |
| FLA | Full load amps, the current at rated load | Close to the original. Use it to check the running motor with a clamp meter |
| RPM | Full load speed. 1075 is a six-pole motor, 825 an eight-pole | Exact. Fan blades are pitched for one speed |
| Speeds | Number of speed taps. Blower motors often have three or four | Same or more |
| Frame | Standard mounting dimensions. 48 frame is about 5-5/8 in across the body, 42 frame about 5 in | Same, or the mount will not fit |
| Rotation | CW or CCW, with the viewing end: SE is shaft end, LE is lead end | Exact, unless the motor is marked reversible |
| Capacitor | Run capacitor the motor needs, in µF and volts | Fit the capacitor the new motor's plate calls for |
| Enclosure | TEAO is totally enclosed air over. OAO is open air over | Same or more enclosed. Outdoor fan motors are enclosed |
| Bearings | Sleeve or ball | Ball for shaft-up or any-angle mounting if in doubt |
| Max ambient | Hottest surrounding air the motor is rated for | Same or higher |
Rotation is the field people get wrong. CCWLE means anticlockwise when you look at the end the wires come out of, which is clockwise viewed from the shaft end. Write down the abbreviation exactly as printed. Also measure the shaft diameter and length, and note whether the shaft points up, down or sideways. A new motor always gets a new run capacitor of the value on its own plate.
CP2PSC and ECM motors
| PSC | Constant-torque ECM | Variable-speed ECM | |
|---|---|---|---|
| What it is | Permanent split capacitor induction motor | Brushless permanent-magnet motor with built-in electronics | Brushless permanent-magnet motor with a control module programmed for the unit |
| Run capacitor | Yes | No | No |
| Speed selection | Line-voltage speed taps | 24 V signal on one of several taps | Commanded by the equipment control board |
| Behavior as static pressure rises | Airflow drops | Holds torque, so airflow drops less | Raises speed to hold programmed airflow |
| Replacement | Universal motors are common | Match the maker's part or a listed replacement | Must match the equipment. The module carries the unit's program |
The three types are not interchangeable by horsepower alone. A PSC motor cannot take the place of an ECM without a kit designed for that conversion, and a variable-speed motor with a generic module will not know the airflow settings for the furnace or air handler it is in. On ECM blowers the motor and the control module are often separate parts, so find out which one failed.
CP3Compressors
Residential and light commercial compressors are hermetic: motor and pump sealed in one welded shell. Most current ones are scroll or rotary designs. Older and larger equipment uses reciprocating compressors, some of them semi-hermetic and repairable. A replacement is defined by:
- Refrigerant. A compressor is built and oiled for specific refrigerants. This is never substituted.
- Capacity. Btu per hour at a stated rating condition, read from the model number.
- Application range. Air conditioning, medium temperature or low temperature. A cooler or freezer compressor is not an air conditioning compressor.
- Electrical. Voltage, phase, RLA (rated load amps) and LRA (locked rotor amps).
- Oil. POE for HFC and A2L refrigerants, mineral or alkylbenzene for R-22.
- Connections and mounting. Suction and discharge tube sizes, foot pattern.
The model and serial on the compressor shell, plus the equipment model, let a counter cross-reference to the current replacement.
Single-phase terminals
The three terminals are common (C), start (S) and run (R). With the wires off and the power locked out, an ohmmeter identifies them:
| Reading between | Result |
|---|---|
| R and S | Highest. It equals the other two added together |
| C and S | Middle |
| C and R | Lowest |
Any continuity from a terminal to the shell means a grounded winding and a failed compressor.
Replacing a compressor opens the refrigerant circuit, so it requires recovery and Section 608 certification. Fit a new liquid line filter drier every time the system is opened. After a burnout, test the oil for acid and add a suction line drier for clean-up. The supplies for that are under chemicals.
CP4Condensate pumps
When condensate cannot drain by gravity, a small pump with a tank and float switch lifts it to a drain. Specify by:
- Lift. The vertical distance from pump to the highest point of the discharge tube, in feet. Pump output falls as lift rises, and every pump has a shut-off head where flow stops.
- Flow at that lift. In gallons per hour, read from the chart on the box at your lift, not the headline figure.
- Voltage. 115 or 230 V.
- Safety switch. A second float that opens a low-voltage circuit if the tank overfills. Wire it to stop the equipment so a failed pump does not flood the ceiling.
- What it is pumping. Condensate from condensing furnaces is acidic. Use a pump rated for it and a neutralizer where the drain requires one.
Ductless indoor units use much smaller pumps made to sit inside or beside the unit. They are chosen by the unit's capacity and by noise rating.
CP5Hydronic circulators
A circulator moves water around a heating or chilled water loop. It does not lift water in a closed loop, it only overcomes pipe friction. Specify by:
| Spec | Meaning |
|---|---|
| Flow and head | Gallons per minute at feet of head. The two are read together from the pump curve |
| Body material | Cast iron for closed heating loops. Bronze or stainless steel for open systems and potable water, where fresh oxygen would rust iron |
| Connection | Flange size and bolt pattern, or union or sweat size |
| Voltage | 115 V on most residential models |
| Speed control | Fixed, three-speed switch, or ECM with automatic pressure control |
The model number on the old circulator's nameplate is the quickest route to a match. Flange-to-flange length matters when the new pump has to fit between existing flanges.