Controls: thermostat wire, capacitors, contactors and switches

Electrical parts are matched by the numbers printed on them. Copy every number from the old part before you leave the unit, and turn the power off at the disconnect before you touch anything.

CT1Thermostat wire colors

Low-voltage control wiring runs at 24 volts AC from a transformer in the furnace or air handler. The terminal letters are consistent across the industry. The colors are only a habit, and installers run out of conductors and improvise, so always confirm the letter at both ends.

  1. RRed24 V power from the transformer
  2. CBlue24 V common, the return side
  3. WWhiteHeat call
  4. YYellowCompressor, cooling call
  5. GGreenIndoor fan
  6. O/BOrangeHeat pump reversing valve
  7. W2BrownSecond stage or auxiliary heat
Terminal letters
TerminalUsual colorWhat it does
R, Rc, RhRed24 V supply. Rc and Rh are separate supplies for cooling and heating on two-transformer systems, jumpered together on single-transformer systems
CBlue, sometimes blackCommon. Completes the circuit so the thermostat has continuous power
W, W1WhiteFirst stage heat
W2, AuxOften brownSecond stage heat, or auxiliary heat on a heat pump
Y, Y1YellowCompressor contactor, first stage
Y2VariesSecond stage compressor
GGreenIndoor blower
OOrangeReversing valve, energized in cooling. The arrangement most heat pump brands use
BVariesReversing valve, energized in heating, on brands that work that way. On some older thermostats B is the common instead, so check the wiring diagram

Thermostat cable is 18 AWG solid copper, named by gauge and conductor count: 18/5 has five conductors. A conventional furnace and air conditioner with a C wire uses five. A heat pump with auxiliary heat can use seven or eight. Pull more conductors than you need today. Spare conductors cost little and save a re-pull.

CT2Capacitors

A run capacitor stays in the circuit whenever a PSC motor or compressor runs. Two numbers define it: capacitance in microfarads (µF, sometimes printed MFD) and voltage rating.

  • Microfarads must match the value the motor nameplate calls for. The tolerance is printed on the capacitor, usually plus or minus 5% or 6%.
  • Voltage rating can go up, never down. A 440 VAC capacitor replaces a 370 VAC one. A 370 does not replace a 440.
  • Shape is fit only. Round and oval cans with the same ratings are electrically the same. Check that it fits the bracket.
Capacitor types
TypeLooks likeMarking exampleTerminals
Single runMetal can, two terminal posts7.5 µF 370 VACTwo, not polarized
Dual runMetal can, three terminal posts45/5 µF 440 VACC (common), HERM (compressor), FAN
StartBlack plastic case, often with a resistor across the terminals88-108 µF 250 VACTwo. In circuit for a moment at start only

On a dual capacitor the larger number serves the compressor and the smaller serves the fan motor. A capacitor that reads outside its tolerance on a meter's capacitance setting, or one with a bulged top, gets replaced. Run and start capacitors do not substitute for each other. The motor side of this is covered under reading a motor nameplate.

CT3Contactors

A contactor is a heavy relay that switches line voltage to the compressor and outdoor fan when the thermostat calls. The definite-purpose contactors used in HVAC are specified by three things:

SpecCommon valuesHow to match
Poles1, 2 or 3Same as the original. Three-pole for three-phase loads
Ampere rating25, 30, 40 A full loadEqual to or higher than the original
Coil voltage24 VAC in most residential units. Also 120 and 208/240 VACExactly the same. A 24 V coil on line voltage burns out at once

A one-pole contactor switches one leg of a 240 V circuit and passes the other straight through on a shunt bar. Parts of the unit stay live even when the contactor is open, which is one more reason to pull the disconnect. Pitted or burnt contacts and a chattering or humming coil are the usual reasons for replacement. Do not file contacts.

CT4Relays, sequencers and transformers

  • General-purpose relays are specified by coil voltage, contact arrangement (SPST, SPDT, DPDT) and contact amp rating. The fan relay in an air handler is typically a 24 V coil switching line voltage to the blower.
  • Sequencers are time-delay relays that bring electric heat strips on in steps. Match the number of switches and the on and off timings.
  • Potential relays and start kits switch a start capacitor out once the compressor is up to speed. Match them to the compressor maker's part number.
  • Transformers are specified by primary voltage (120, 208 or 240 V, often multi-tap), secondary voltage (24 V) and capacity in volt-amperes. A 40 VA transformer supplies about 1.6 amps at 24 V. Adding accessories such as humidifiers or zone dampers can exceed that. Replace with equal or higher VA.

Most control boards protect the 24 V circuit with a 3 or 5 amp blade fuse. A fuse that blows again straight away means a short in the low-voltage wiring, often where the cable rubs on the outdoor unit cabinet.

CT5Pressure and temperature controls

ControlWhat it doesSpecified by
High-pressure switchOpens to stop the compressor when discharge pressure is too highCut-out and cut-in in psig, auto or manual reset, connection type, refrigerant
Low-pressure switchOpens when suction pressure falls, as on loss of chargeCut-out and cut-in in psig, connection type
Fan cycling controlCycles the condenser fan to hold head pressure in cool weatherCut-in and cut-out pressure or temperature
Limit switchOpens the burner or heater circuit on over-temperatureOpening temperature, differential, probe length, mounting
Rollout switchOpens if flame leaves the burner box. Manual resetOpening temperature, mounting
Defrost thermostatTells a heat pump defrost board the coil is cold enough to frostClose and open temperatures, tube size it clips to
Hot surface ignitorGlows to light the gas burnerVoltage, material (silicon carbide or silicon nitride), bracket and plug
Flame sensor, thermocoupleProves flame so the gas valve may stay openLength, bracket, connection. A thermocouple generates about 30 millivolts

The difference between cut-in and cut-out is the differential. Fixed switches have both stamped on the body. Adjustable ones have a scale for each. Pressure settings depend on the refrigerant, so a switch from an R-22 unit is not right for a system on R-410A or an A2L refrigerant. A safety switch that keeps tripping is reporting a fault somewhere else. Replacing it rarely fixes anything, and bypassing one is never a repair.