DS1Sheet metal gauges
Duct is made from galvanized steel, which is steel sheet with a zinc coating. Thickness is given as a gauge number that runs backwards: the lower the number, the thicker the sheet.
| Gauge | Nominal thickness, in | Edge view, relative | Where you see it |
|---|---|---|---|
| 30 | 0.0157 | Light residential round pipe and elbows | |
| 28 | 0.0187 | Residential round pipe, small rectangular duct | |
| 26 | 0.0217 | Residential trunk duct, plenums, larger round pipe | |
| 24 | 0.0276 | Light commercial rectangular duct | |
| 22 | 0.0336 | Larger commercial duct | |
| 20 | 0.0396 | Large or higher-pressure duct, equipment curbs |
The gauge required for a given duct depends on its size, its pressure class and how it is reinforced. Mechanical codes and the SMACNA duct construction standards set those minimums. Wider duct needs heavier metal or cross-breaks and stiffeners so the flat sides do not drum.
The zinc coating has its own designation. G60 and G90 mean 0.60 and 0.90 ounces of zinc per square foot, counting both sides together. G90 is the heavier coating and resists corrosion longer in damp locations.
Round pipe and fittings
Round pipe is sold by diameter and length, with one end crimped. The crimped end points in the direction of airflow, so each joint laps like roof shingles and does not catch air. Fasten each joint with at least three sheet metal screws, then seal it. The common fitting names:
| Fitting | What it does |
|---|---|
| Starting collar, take-off | Connects a round branch to a trunk duct or plenum |
| Adjustable elbow | Segmented elbow that twists to any angle up to 90 degrees |
| Wye, tee | Splits one run into two |
| Reducer | Changes diameter |
| Boot | Transitions from round duct to a rectangular register opening |
| Damper | Blade inside the duct for balancing airflow |
| S-cleat and drive cleat | Slip-on strips that join sections of rectangular duct |
DS2Flexible duct
Flex duct has three layers: a wire-helix inner core, fiberglass insulation and an outer vapor-barrier jacket. It is sold boxed, commonly in 25 ft lengths, by inside diameter and insulation R-value.
| Spec | Options |
|---|---|
| Diameter | 4 in upward, in whole and even inch sizes |
| Insulation | R-4.2, R-6 and R-8 |
| Jacket | Gray or black polyethylene, or reflective foil-faced |
| Listing | UL 181 Class 1 air duct, printed along the jacket |
Flex duct performs well only when installed tight. The rules that matter:
- Pull it to full length and cut off the excess. Compressed flex has far more airflow resistance than the same duct stretched out.
- Support it at intervals of no more than 4 ft, on straps at least 1-1/2 in wide, with no more than 1/2 in of sag per foot between supports.
- Keep bends gentle, with a centreline radius of at least one duct diameter.
- At each connection, fasten the inner core to the collar with a clamp or tie and seal it, then pull the insulation and jacket over and secure the jacket separately.
Energy codes commonly require R-8 for ducts in attics and R-6 in other unconditioned spaces. Check the local requirement before buying a truckload of R-4.2.
DS3Duct board
Duct board is rigid fiberglass with a foil-scrim-kraft facing on the outside. It is cut with grooving tools and folded into rectangular duct and plenums, so the duct is its own insulation.
| Thickness | R-value |
|---|---|
| 1 in | 4.3 |
| 1-1/2 in | 6.5 |
| 2 in | 8.7 |
It is quiet and quick to fabricate. It is also easier to damage than metal and cannot be cleaned as aggressively, and its joints depend entirely on the closure system. Seams are stapled and then sealed with a tape or mastic listed for rigid fiberglass duct.
DS4Mastic, foil tape and UL 181
UL 181 is the standard that duct materials and their closures are listed to. The marking printed on the tape or pail tells you what it is approved to seal:
| Marking | Product | Listed for |
|---|---|---|
| UL 181A-P | Pressure-sensitive foil tape | Rigid fiberglass duct board |
| UL 181A-H | Heat-activated foil tape | Rigid fiberglass duct board |
| UL 181A-M | Mastic | Rigid fiberglass duct board |
| UL 181B-FX | Pressure-sensitive tape | Flexible duct |
| UL 181B-M | Mastic | Flexible duct |
Mastic is a thick paste brushed over joints and seams, most often water-based. It fills irregular gaps, sticks to slightly dusty metal and stays sealed for the life of the duct. Bridge any gap wider than about 1/8 in with fiberglass mesh tape and mastic over it. Its drawbacks are mess and drying time.
Foil tape is faster and cleaner. It needs a clean, dry, oil-free surface and firm pressure from a squeegee to bond, and it does not bridge gaps or wrap awkward shapes well. Choose a tape with a UL 181 marking. Ordinary cloth-backed "duct tape" is not a listed closure and dries out and falls off, despite the name.
Sealing order on sheet metal: mechanical fasteners first, then sealant on every transverse joint, the longitudinal seams, and around every take-off and boot. Leaky return ducts pull in attic or crawlspace dust that loads the filter and the coil.
DS5Insulating metal duct
Bare metal duct in an unconditioned space is wrapped with fiberglass duct wrap, a blanket with a foil vapor-barrier facing. It is sold by thickness and installed R-value. Wrap it without squeezing it thin, since compressed insulation loses R-value, and tape every seam in the facing so humid air cannot reach the cold metal and condense. Duct liner is a different product, fixed to the inside of the duct for sound control as well as insulation.
Duct size comes from an airflow calculation for each room, not from what was there before. The equipment page covers the load calculation that comes first.