Equipment: classes a supply house stocks and how to specify them

Whole units are specified by capacity, voltage and phase, refrigerant, and what they must match. Capacity comes from a load calculation, and the electrical figures come straight off the data plate.

EQ1Equipment classes

ClassWhat it isWhere the parts are
Split systemAn outdoor condensing unit or heat pump joined by refrigerant lines to an indoor coil with a furnace or air handlerTwo matched halves, plus a field-installed line set
Packaged unitAll components in one outdoor cabinet, on a roof curb or a ground slab, connected to the building by duct onlyOne cabinet. Factory charged
Ductless mini splitAn outdoor unit serving one or more indoor units that blow directly into the roomOutdoor unit, indoor units, a line set and control cable per indoor unit
Ice machineA refrigeration system that freezes water into cubes, nuggets or flakesIce-making head, storage bin, water filter
Portable spot coolerA self-contained air conditioner on wheels for temporary or emergency coolingOne cabinet, with flexible ducts

EQ2Specifying capacity and efficiency

Cooling capacity is given in Btu per hour or in tons, where one ton is 12,000 Btu per hour. Most model numbers carry the capacity in thousands of Btu per hour, so 036 in a model number usually means a 3 ton unit.

Digits in model numberBtu/hTons
01818,0001.5
02424,0002
03030,0002.5
03636,0003
04242,0003.5
04848,0004
06060,0005

The right capacity for a building comes from a room-by-room load calculation such as ACCA Manual J, which accounts for insulation, windows, air leakage and climate. Copying the size of the old unit copies any mistake made when it was installed, and square-feet-per-ton rules ignore everything that differs between two houses. Oversized cooling equipment cycles on and off and removes less humidity.

Efficiency ratings since 2023 are SEER2 and EER2 for cooling and HSPF2 for heat pump heating. They come from a test procedure with higher duct static pressure than the older SEER and HSPF, so the numbers are not directly comparable with old labels. Federal minimums for residential split air conditioners differ by region: 13.4 SEER2 in the North and 14.3 SEER2 in the Southeast and Southwest for units under 45,000 Btu per hour. Split heat pumps have a national minimum of 14.3 SEER2 and 7.5 HSPF2. Gas furnaces are rated by AFUE, the share of fuel energy delivered as heat over a season.

Refrigerant

Newly manufactured residential air conditioners and heat pumps use R-454B or R-32. Both are A2L refrigerants, meaning low toxicity and mild flammability, and the equipment is built for them with features such as leak sensors on many indoor units. R-410A equipment is no longer manufactured for new residential systems. The halves of a system must use the same refrigerant, so an R-454B outdoor unit cannot be paired with an existing R-410A indoor coil. The background is under refrigerant status.

EQ3Reading the data plate

Outdoor unit data plate
FieldMeaningUsed for
Model and serialIdentifies the exact unit and its build dateEvery parts lookup and warranty question
Volts, phase, HzPower supply required: commonly 208/230 V single phase for homes, three phase in commercial buildingsMust match the building supply
MCAMinimum circuit ampacitySizing the branch circuit conductors
MOP or max fuse/breakerMaximum overcurrent protectionThe largest breaker or fuse allowed
Compressor RLA and LRARated load and locked rotor ampsDiagnosis, and matching a compressor
Fan motor FLA and HPFull load amps and horsepowerMatching a motor
Refrigerant and factory chargeType and weight of refrigerant shipped in the unitCharging, recovery, and choosing tools rated for it
Design or test pressuresHigh and low side limitsThe ceiling for a nitrogen pressure test

Three-phase and single-phase versions of the same model differ by one character in the model number. Read it twice.

EQ4Split and packaged systems

A split system only delivers its rated capacity and efficiency as a matched combination: a specific outdoor unit with a specific indoor coil and blower. Matched combinations are listed in the AHRI directory, each with a reference number. Ask for that number when buying both halves, and check that the indoor coil's metering device is the one the match requires.

For the indoor side, also specify:

  • Airflow direction. Upflow, downflow or horizontal, and for horizontal, left or right.
  • Cabinet width. Furnace and coil cabinets come in standard widths, and the coil should match the furnace it sits on.
  • Furnace type. Input in Btu per hour, AFUE, and whether it is a condensing model, which vents through plastic pipe and produces acidic condensate.
  • Electric heat. Kilowatts of the heater kit in an air handler, which sets a large part of the circuit size.
  • Line set. Diameters and length within the maker's limits. See the tube chart.

Packaged units are specified the same way for capacity and electrical supply, plus heat type (gas, electric or heat pump), supply and return duct configuration (side or bottom discharge) and the roof curb they sit on. When replacing a rooftop unit, the new unit's footprint rarely matches the old curb exactly, and a curb adapter is the usual answer.

EQ5Ductless systems

Ductless equipment is specified by the capacity of each indoor unit and the outdoor unit that serves them. Decide:

  • Single-zone or multi-zone. One indoor unit per outdoor unit, or several. A multi-zone outdoor unit has a list of allowed indoor unit combinations.
  • Indoor unit style. High wall, ceiling cassette, floor console or concealed ducted.
  • Voltage. 115 V on some small units, 208/230 V on most.
  • Line set length and lift. Each model has a minimum and maximum length and a maximum height difference.
  • Low-temperature heating. The outdoor temperature down to which the unit is rated to heat.

Most ductless line sets are field-flared and the system is evacuated with a vacuum pump before the factory charge is released. Some systems are sold for owner installation with factory-charged quick-connect line sets instead. Zone Air, for example, uses R-454B and supplies pre-charged line sets cut to length from 5 to 75 ft.

EQ6Ice machines

Commercial ice machines are either modular, an ice-making head that sits on a separate bin or dispenser, or self-contained undercounter units with a built-in bin. Specify:

  • Production. Pounds of ice per 24 hours. Output falls as air and water get warmer, so compare figures at the same conditions. The standard rating condition is 90 °F air and 70 °F water. The larger figure on a brochure is often at 70 °F air and 50 °F water.
  • Storage. Bin capacity in pounds, sized to the busiest period and not to daily production.
  • Ice form. Full or half cube, nugget, or flake.
  • Condenser type. Air-cooled, water-cooled, or remote air-cooled with the condenser outdoors.
  • Utilities. Voltage and phase, water supply with a filter, and a floor drain.

EQ7Portable spot coolers

A spot cooler is for a server closet whose main cooling failed, or a work area during a repair. It rejects heat as hot air, so that air has to go somewhere:

  • Condenser air. Air-cooled models duct hot air out of the room, often into the ceiling plenum. If that air cannot leave the space, the unit heats the room it is cooling.
  • Condensate. Collected in a tank that shuts the unit off when full, or pumped away with a condensate pump.
  • Power. Small units run on a standard 115 V receptacle. Larger ones need 208/230 V or three-phase power, with the matching plug.
  • Capacity. About 1 to 5 tons. Size to the heat load of the equipment and people in the space.