Northaire Supply

HVAC/R parts and supplies reference

All categories / Certification and reclaim

EPA 608 certification and refrigerant reclaim

Anyone who opens a refrigerant circuit, or buys refrigerant, needs EPA Section 608 certification. Refrigerant that comes out of a system is recovered into a cylinder and, if it is to be resold, sent to a certified reclaimer.

SV1Section 608 certification types

Section 608 of the Clean Air Act makes it illegal to knowingly vent refrigerant and requires technicians who maintain, service, repair or dispose of equipment containing refrigerant to be certified. The certification type follows the kind of equipment.

Section 608 technician certification
TypeCoversExamples
Type ISmall appliances: factory-sealed, with a charge of 5 lb or lessHousehold refrigerators, window units, dehumidifiers, vending machines
Type IIHigh-pressure and very high-pressure appliances, other than small appliances and motor vehicle air conditioningResidential split systems, heat pumps, rooftop units, supermarket refrigeration
Type IIILow-pressure appliancesLow-pressure centrifugal chillers
UniversalAll of the aboveWhat most working technicians hold

Motor vehicle air conditioning is a separate program under Section 609.

How the exam works

  • The exam has a Core section plus one section for each type. Each section is 25 multiple-choice questions.
  • The pass mark is 70%, which is 18 correct out of 25, in each section you want credit for.
  • Universal means passing Core, Type I, Type II and Type III.
  • Exams are given by certifying organizations approved by the EPA, not by the EPA itself. Many trade schools and supply houses host proctored sessions.
  • Type I alone can be taken as an open-book test through some organizations, with a higher pass mark. Types II and III must be proctored.
  • The certification does not expire. If you lose the card, the organization that tested you issues a replacement.

Core covers ozone depletion and climate effects, the regulations, the three R's below, recovery equipment, cylinder safety, leak detection and shipping. The type sections cover recovery requirements, leak repair rules and safe practice for that class of equipment.

What the card is for at the counter

Sales of refrigerant are restricted to certified technicians, or to employers who have a certified technician on staff. Since 2018 the restriction has covered HFC refrigerants such as R-410A and R-134a as well as the older ozone-depleting ones. Sellers must verify certification and keep a record, so expect to show the card or have it on file. The exception is small cans of motor vehicle refrigerant with self-sealing valves. Parts that do not contain refrigerant, such as controls, filters and motors, need no certification to buy.

SV2Refrigerant status

Common refrigerants in late 2026
RefrigerantSafety classGWPStatus
R-22A11,810Production and import ended on 1 January 2020. Supply for service is reclaimed or stockpiled gas only
R-410AA12,088Being phased down. Not used in newly manufactured residential systems. Still supplied for servicing existing equipment
R-454BA2L466Used in new residential and light commercial air conditioners and heat pumps
R-32A2L675Used in new residential and ductless equipment. Also a component of R-410A and R-454B
R-134aA11,430Being phased down. Found in older refrigeration and chillers
R-404AA13,922Being phased down. Found in existing commercial refrigeration

GWP is global warming potential compared with carbon dioxide. The phase-down of HFCs under the AIM Act cuts the national supply in steps, to 15% of the baseline by 2036, and separate EPA rules cap the GWP of refrigerant in new comfort cooling equipment at 700. That cap is why new equipment moved to R-454B and R-32.

What A2L means

The letter is toxicity (A is lower) and the number is flammability: 1 does not propagate flame, 2L is mildly flammable with a low burning velocity, 3 is highly flammable like propane. A2L refrigerants are hard to ignite, but the rules of work change:

  • Use recovery machines, vacuum pumps and leak detectors rated for A2L refrigerants.
  • Ventilate the work area and keep ignition sources away while the circuit is open.
  • Cylinders for flammable refrigerants carry a red band or red top.
  • No refrigerant is a drop-in for another. R-454B and R-32 do not go into an R-410A system, and neither goes into an R-22 system.

R-410A and R-454B are blends and are charged as liquid so the mix stays in proportion.

SV3Cylinder colors

  • R-22light green
  • R-410Arose
  • R-134alight blue
  • R-404Aorange
  • R-407Cbrown
  • Current standardone gray-green for all
  • Flammable (A2L, A3)red band at the top
  • Recovery cylindergray with yellow top
The first five are the older colors still found on cylinders in service trucks and storage. Under the current industry guideline, new cylinders are a single light gray-green whatever they hold, so the color no longer identifies the contents.

Identify refrigerant by the label and the stamped markings, never by paint. Disposable cylinders are single-use and must not be refilled. Recovery cylinders are refillable, built and marked for the purpose, and need periodic requalification, with the test date stamped on the collar.

SV4Recover, recycle, reclaim

The three terms are not interchangeable
TermWhat happensWho does itWhat the refrigerant can be used for
RecoverRefrigerant is removed from a system into an external cylinder, in whatever condition it is inThe certified technician, with a recovery machineReturned to the same system, or held for recycling or reclaim
RecycleRecovered refrigerant is cleaned by separating oil and passing it through filter driersThe technician, usually on siteEquipment belonging to the same owner
ReclaimRefrigerant is reprocessed to the purity of new product (AHRI Standard 700) and verified by laboratory analysisAn EPA-certified reclaimerSale to anyone entitled to buy refrigerant

Used refrigerant cannot change owners unless it has been reclaimed. That rule is what makes reclaim the route for gas recovered from scrapped equipment, and reclaimed gas is now the only source of R-22.

SV5How a reclaim drop-off works

Many supply houses act as collection points for reclaimers. The routine is much the same everywhere:

  1. Recover into a clean, in-date recovery cylinder. Fill to no more than 80% of its capacity by weight, checking on a scale.
  2. Keep one refrigerant per cylinder. Mixed refrigerants are difficult to separate and are often charged as a disposal cost instead of earning a credit.
  3. Tag the cylinder with the refrigerant type and the weight recovered.
  4. Take the full cylinder to the collection point. It is weighed, and its contents may be tested for purity.
  5. You receive an empty cylinder or your own back later, and a record of what was turned in.

Keep those records. Technicians who dispose of mid-sized appliances must keep records of the refrigerant recovered, and building owners with larger systems have their own leak and service record duties.