PR1Category index
| Category | What is in it | You specify it by |
|---|---|---|
| Filters | Throwaway, pleated and deep media filters, washable filters | Actual size, depth, MERV |
| Controls | Thermostats and wire, capacitors, contactors, relays, transformers, pressure and limit switches, ignitors | Voltage, microfarads, amps, poles, cut-in and cut-out |
| Chemicals | Coil cleaners, condensate pan and drain treatments, leak detectors, oils | Coil type and location, refrigerant, pH class |
| Compressors, motors, pumps | Compressors, fan and blower motors, condensate pumps, hydronic circulators | Nameplate data, refrigerant, lift and flow |
| Duct and sheet metal | Round pipe and fittings, flex duct, duct board, tapes, mastic, insulation | Diameter, gauge, R-value, UL 181 listing |
| Equipment | Split and packaged systems, ductless, ice machines, portable spot coolers | Capacity, voltage and phase, refrigerant, matched combination |
| Certification and reclaim | EPA Section 608, refrigerant status, recovery cylinders, reclaim | Certification type, refrigerant, cylinder weight |
PR2ACR copper tube sizes
ACR tube, the copper made for air conditioning and refrigeration, is named by its actual outside diameter (OD). Plumbing copper (Types K, L and M) is named by a nominal size that is 1/8 in smaller than its OD. The two systems overlap, which is why a 7/8 ACR suction line and a "3/4 inch" plumbing pipe are the same diameter. Ask for tube by OD and say "ACR" and nobody has to guess.
| ACR size (OD, in) | OD, decimal in | Same OD as plumbing nominal | Wall, in |
|---|---|---|---|
| 1/4 | 0.250 | 1/8 | 0.030 |
| 5/16 | 0.312 | No plumbing equivalent | 0.032 |
| 3/8 | 0.375 | 1/4 | 0.032 |
| 1/2 | 0.500 | 3/8 | 0.032 |
| 5/8 | 0.625 | 1/2 | 0.035 |
| 3/4 | 0.750 | 5/8 | 0.035 |
| 7/8 | 0.875 | 3/4 | 0.045 |
| 1-1/8 | 1.125 | 1 | 0.050 |
| 1-3/8 | 1.375 | 1-1/4 | 0.055 |
What makes tube "ACR" is not only the naming. It is cleaned and dehydrated at the mill and shipped sealed, with capped ends on straight lengths and plugged ends on coils, so the inside is dry and free of oil and scale. Plumbing tube from the same rack size is not prepared that way and does not belong in a refrigerant circuit. Keep the caps on until the moment you connect it.
Soft or hard drawn
| Soft (annealed) | Hard drawn | |
|---|---|---|
| Sold as | Coils, commonly 50 ft | Straight lengths, commonly 20 ft |
| Bends | By hand or with a bender | Does not bend. Use fittings |
| Joins by | Flare or braze | Braze. It cannot be flared without annealing |
| Typical use | Line sets, short runs to the unit | Long exposed runs, risers, commercial piping |
Pre-insulated line sets are soft ACR tube in pairs, a small liquid line and a larger insulated suction (vapor) line. They are ordered by both diameters and the length, for example 3/8 by 3/4 by 50 ft. The equipment installation manual gives the line sizes for the capacity and length of run. Do not size from the old line set alone.
Flare or braze
- Flare. A 45 degree flare on soft tube, sealed by a flare nut against a matching fitting. Standard on ductless equipment. Use a flaring tool made for current high-pressure refrigerants, deburr without thinning the tube, and tighten with a torque wrench to the equipment maker's value. A flare can be remade. A flare that weeps is the most common ductless leak.
- Braze. A permanent joint made above 840 °F with filler metal. Copper to copper is done with a phosphorus-bearing copper alloy (BCuP), which needs no flux. Copper to brass or steel needs a silver alloy (BAg) and flux. Flow dry nitrogen through the tube while brazing so black oxide scale does not form inside and end up in the metering device.
- Press. Mechanical press fittings rated for refrigerant are a third option. They need the matching tool and jaws and must be listed for the refrigerant and pressure.
Soft solder of the plumbing kind is not used on refrigerant lines.
PR3What to bring to any counter
Parts are found by number first, description second. In order of usefulness (the part-by-part version is on before you go to the counter):
- The equipment data plate: brand, full model number and serial number. A phone photo is fine if it is sharp.
- The old part, with its label. Original equipment part numbers cross-reference to universal replacements.
- The electrical facts: line voltage, phase, and control voltage.
- For anything touching the refrigerant circuit, the refrigerant type from the data plate and your Section 608 card.
- Measurements where numbers are missing: shaft diameter, body diameter, mounting hole spacing, tube OD.
Category pages go deeper: controls for anything electrical, compressors, motors and pumps for nameplates, and equipment for whole units.