FL1Nominal and actual size
The big numbers on a filter are the nominal size, rounded up to whole inches. The filter itself is smaller so it slides into the slot. A filter sold as 16 x 25 x 1 usually measures about 15-1/2 x 24-1/2 x 3/4. The actual size is printed in smaller type on the frame.
| Nominal depth | Typical actual depth | Notes |
|---|---|---|
| 1 in | 3/4 in | Standard return grille and furnace rack filter |
| 2 in | 1-3/4 in | Common in light commercial units |
| 4 in | 3-3/4 in | Generic deep pleat. Cabinet-specific media can run 4-3/8 in or more |
| 5 in | Varies by cabinet | Order by the cabinet brand and model, or measure the old media |
Undercut varies between makers, and deep media made for a particular filter cabinet often does not follow these rules at all. When there is no old filter, measure the slot opening and order the nominal size that matches it. When there is an old filter, order by its printed actual size. Written order is always the two face dimensions, then depth. The airflow arrow on the frame points toward the blower.
FL2What MERV numbers mean
MERV, the minimum efficiency reporting value, comes from the ASHRAE 52.2 test. The test measures how much of three particle size ranges a filter captures: E1 is 0.3 to 1.0 micron, E2 is 1.0 to 3.0 micron and E3 is 3.0 to 10 micron. A higher MERV must capture more of the smaller ranges.
| MERV | E1, 0.3 to 1 µm | E2, 1 to 3 µm | E3, 3 to 10 µm | Typical product |
|---|---|---|---|---|
| 1 to 4 | not rated | not rated | under 20% | Flat fiberglass throwaway |
| 6 | not rated | not rated | 35% | Basic pleat |
| 8 | not rated | 20% | 70% | Standard pleat |
| 11 | 20% | 65% | 85% | Better pleat |
| 13 | 50% | 85% | 90% | High-efficiency pleat, deep media |
| 14 | 75% | 90% | 95% | Commercial bag or rigid cell |
| 16 | 95% | 95% | 95% | Hospital-grade final filter |
Pollen and lint are mostly E3 particles. Fine dust and much of what is in smoke are E1. That is why MERV 13 is the usual target when smoke or fine particles are the concern, and why a MERV 8 does little for them. HEPA filters are tested differently (99.97% at 0.3 micron) and are not on the MERV scale. They are too restrictive for an ordinary residential blower unless the system was designed around them.
Retail packaging often shows a store-specific rating system instead of MERV. Those scales do not convert exactly. Look for the MERV number in the fine print.
FL3Pressure drop
Every filter resists airflow. The resistance is its pressure drop, given in inches of water column (in. w.c.) at a stated airflow. Three things set it:
- Face velocity. The same filter has a much higher drop at 500 feet per minute than at 300. Velocity is airflow in cfm divided by filter face area in square feet.
- Media area. More pleats and more depth mean more media for the air to pass through, so a lower drop. A 4 in MERV 13 commonly has a lower drop than a 1 in MERV 13 in the same opening.
- Loading. Drop rises as the filter fills with dust. The clean figure on the spec sheet is the starting point, not the average.
Many residential furnaces and air handlers are rated to deliver their airflow against about 0.5 in. w.c. of total external static pressure, and the filter is only one part of that total alongside the coil, ducts and grilles. A restrictive filter in an undersized return is a frequent cause of low airflow, frozen evaporator coils and tripped furnace limit switches.
Checking filter area
A common design airflow for cooling is about 400 cfm per ton. Keeping filter face velocity near 300 feet per minute or below gives a pleated filter room to work:
| System | Airflow, cfm | Filter area at 300 fpm | Example filter face |
|---|---|---|---|
| 2 ton | 800 | 2.7 sq ft | 20 x 20 |
| 3 ton | 1,200 | 4.0 sq ft | 20 x 30, or two 16 x 20 |
| 4 ton | 1,600 | 5.3 sq ft | Two 20 x 20 |
| 5 ton | 2,000 | 6.7 sq ft | Two 20 x 25 |
Many installed systems have less filter area than this. If yours does, a lower MERV or a deeper filter cabinet is the honest fix, not a "high-flow" label. Return-side changes belong with the rest of the duct system.
FL4Filter types at the counter
| Type | MERV range | Good for | Watch for |
|---|---|---|---|
| Fiberglass throwaway | 1 to 4 | Protecting the blower and coil from lint | Does almost nothing for fine dust |
| 1 in pleated | 6 to 13 | Most residential slots | High drop at MERV 11 and up in small returns |
| Deep pleated media, 4 to 5 in | 8 to 16 | High efficiency at low drop, long change interval | Needs a media cabinet. Sizes are cabinet-specific |
| Washable | Usually low | Reuse where lint is the main load | Must be fully dry before going back in |
| Bag and rigid cell | 11 to 16 | Commercial air handlers | Needs a prefilter and holding frames |
Change interval depends on dust load, not the calendar printed on the wrapper. Check monthly at first, and change when the media is visibly gray across the face. Evaporator coils downstream of a missing or bypassed filter end up needing coil cleaner.